Series 60-AS: Soft Start Electric Motor Fire Pump Controller
Request Quote
Request Quote
Features
- Soft start significantly reduces the starting current.
- Adjustable initial start voltage from 40 to 80%.
- Lighter weight and more compact size than an autotransformer starter.
- 3 years warranty.
- Robust and secure design, high-tech with the best quality.
The Serie 60-AS panels include:
- Soft starter
- Manual or automatic stop selector.
- Manual stop button.
- Suction low-level detection and indication.
- Control module.
- 0-6 Min. stop delay adjustment.
- Manual-Off-Automatic operation selector.
- Pilot lights for: Pump operating, Selector in automatic, and Suction low-level.
- Modbus: Network connection for monitoring with Modbus RTU via RS-485 or Modbus TCP-IP via Ethernet. (Optional)
- NEMA 4(IP66) red metal cabinet, dust, and water-resistant.
- 1PDT contacts for remote signaling of: Pump operating and Suction low-level. (Optional).
Description
The Serie 60-AS fire control panels with soft starter for electric motor control the automatic operation of electric motor-operated fire pumps. It detects the water level in the tank, has a selector for Manual-Off-Automatic operation, indicator lights for the selector in automatic, operation, and low suction level. Manual or automatic stop can be selected after an adjustable stop delay.
The start signal is obtained from a pressure switch placed in the fire network. When the pressure in the system is restored, the control starts counting the time set as the stop delay. Once this time has elapsed, the pump is turned off. If manual stop was selected, the pump does not turn off until the stop button is pressed.
The “Low Suction Level” is only indicated with the pilot light; by standard, the equipment does not stop the pump for this fault, only indicates it unless it is in stop delay.
Advantages
- Better control of start and stop, as the voltage gradually changes in a smooth ramp, reducing current peaks, smoothing stops, and decreasing maximum demand, achieving a smoother start and stop (See graph on page 17).
- The initial voltage is adjustable from 40 to 80%.
- Lower weight and more compact size.
This panel can be ordered with a network connection for monitoring via Modbus RTU using RS-485 or Modbus TCP-IP via Ethernet.
The Serie 60-AS Fire Control Panels include most of the requirements indicated by the N.F.P.A. in its pamphlet #20.
Optional Equipment
- Modbus: Network connection for monitoring via Modbus RTU using RS-485 or Modbus TCP-IP via Ethernet.
- Safety disconnect switch that disconnects power when opening the cabinet.
- Magnetic switch. (Available from 12 Amp onwards.)
- Remote signaling contacts.
- Pressure switch 1-10 kg (15-147 PSI).
- PD-640 protector against high voltage discharges.
- Remote alarm for low voltage, imbalance, and phase failure.
- Three-phase RMS digital voltmeter with max/min voltage and frequency meter, mounted on the cabinet door.
- Three-phase RMS digital ammeter with max current recording, mounted on the cabinet door.
| CF | AMP. 220 V | AMP. 440 V |
| 30 | 80 | 50 |
| 40 | 105 | 60 |
| 50 | 140 | 65 |
| 60 | 160 | 80 |
| 75 | 95 | |
| 100 | 125 |
| TECHNICAL SPECIFICATIONS | |
| Power supply voltage | 220/440V ± 10% |
| Rated battery voltage | From 40 to 80% |
| Starting ramp | Adjustable from 0 to a maximum of 15 seconds. |
| Duck ramp | 5 seconds fixed. |
| Startup frequency | 15/hour maximum, heavy start: 10/hour maximum. |
| Cabinet | NEMA 4(IP66) dust and water resistant |
| Operating temperature | -15 to + 40 º |
Pump Operating and Low Suction Level indication with 22mm pilot lights.
NEMA 4(IP66) metal cabinet, dust, and water-resistant.